Display method : 4-digit 7-segment LED
Control method : ON/OFF control, P, PI, PD, PID control
Input specification : Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle : 100ms
Control output : Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF]
Power supply : 100-240VAC~ 50/60Hz
Approval :

...
Display method 4-digit 7-segment LED
Control method ON/OFF control, P, PI, PD, PID control
Input specification Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle 100ms
Control output Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF]
Option output Alarm 1/2
Power supply 100-240VAC~ 50/60Hz
Approval  
Display accuracy_RTD •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Display accuracy_Thermocouple •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Hysteresis(adjustable sensitivity) 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band 0.1 to 999.9℃/℉
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Insulation type Double insulation or reinforced insulation(mark: , dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
Weight Approx. 203g(approx. 133g)

※In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle control, phase control) is available to select.
※Display accuracy:
At room temperature (23℃ ±5℃)
• Thermocouple R (PR), S (PR), below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
• Thermocouple R (PR), S (PR), over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
• Thermocouple L (IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit

Out of room temperature range
• Thermocouple R (PR), S (PR), below 200℃: (PV ±1.0% or ±6℃, select the higher one) ±1-digit
• Thermocouple R (PR), S (PR), over 200℃: (PV ±0.5% or ±5℃, select the higher one ±1-digit
• Thermocouple L (IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
For TCN4S-□-P, add ±1℃ by accuracy standard.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.